Site Name: Richmond NSW, Building Name: OCT-2AHU-2CH-API-Test04, Location Template: MELBOURNE AIRPORT, Weather File: AUS_MELBOURNE_IWEC
Report generated: 17/01/2026 2:52:41 PMWinter clothing level: 1, Summer clothing level: 0.5, Metabolic Rate: NCC Office Met Rates, Comfort Radiant Temperature Weighting: 2-Surface with largest window
Some zones had Occupation Schedule names that marked them as 'Do not report'. The following zones are not included in the analysis: 00-GROUNDFloor01:CENNorth
Not all zones pass temperature check - Building : FAIL
| Block | Zone | Floor Area (m²) | Fraction Total Floor Area | Building Class | Operation Hours | Operation Hours T below target | Operation Hours T in target range | Operation Hours T above target | Fraction Operation Hours T in target range | Zone temperature meets Section J target (T in target range ≥ 98 % Operation Hours) |
|---|---|---|---|---|---|---|---|---|---|---|
| 00-GROUNDFloor01 | EastNorth 1 | 41.9 | 0.02 | Class 5 | 2610 | 10 | 2600 | 0 | 0.996 | PASS |
| 00-GROUNDFloor01 | EastNorth | 31.5 | 0.02 | Class 5 | 2610 | 9 | 2601 | 0 | 0.997 | PASS |
| 00-GROUNDFloor01 | EastSouth 1 | 26.9 | 0.01 | Class 5 | 2610 | 9 | 2601 | 0 | 0.997 | PASS |
| 00-GROUNDFloor01 | CENSouth | 228.7 | 0.13 | Class 5 (TO) | 2610 | 0 | 2610 | 0 | 1.000 | PASS |
| 00-GROUNDFloor01 | EastSouth | 41.4 | 0.02 | Class 5 | 2610 | 93 | 2517 | 0 | 0.964 | FAIL |
| 00-GROUNDFloor01 | WestS 1 | 42.8 | 0.02 | Class 5 | 2610 | 78 | 2532 | 0 | 0.970 | FAIL |
| 00-GROUNDFloor01 | WestS | 26.6 | 0.01 | Class 5 | 2610 | 8 | 2602 | 0 | 0.997 | PASS |
| 00-GROUNDFloor01 | WestN 1 | 31.7 | 0.02 | Class 5 | 2610 | 8 | 2602 | 0 | 0.997 | PASS |
| 00-GROUNDFloor01 | WestN | 41.9 | 0.02 | Class 5 | 2610 | 8 | 2602 | 0 | 0.997 | PASS |
| 01-TYPICALFloor | CENNorth | 257.5 | 0.14 | Class 5 | 2610 | 0 | 2610 | 0 | 1.000 | PASS |
| 01-TYPICALFloor | EastNorth 1 | 41.9 | 0.02 | Class 5 | 2610 | 10 | 2600 | 0 | 0.996 | PASS |
| 01-TYPICALFloor | EastNorth | 31.5 | 0.02 | Class 5 | 2610 | 9 | 2601 | 0 | 0.997 | PASS |
| 01-TYPICALFloor | EastSouth 1 | 26.9 | 0.01 | Class 5 | 2610 | 9 | 2601 | 0 | 0.997 | PASS |
| 01-TYPICALFloor | CENSouth | 228.7 | 0.13 | Class 5 | 2610 | 0 | 2610 | 0 | 1.000 | PASS |
| 01-TYPICALFloor | EastSouth | 41.4 | 0.02 | Class 5 | 2610 | 102 | 2508 | 0 | 0.961 | FAIL |
| 01-TYPICALFloor | WestS 1 | 42.8 | 0.02 | Class 5 | 2610 | 85 | 2525 | 0 | 0.967 | FAIL |
| 01-TYPICALFloor | WestS | 26.6 | 0.01 | Class 5 | 2610 | 9 | 2601 | 0 | 0.997 | PASS |
| 01-TYPICALFloor | WestN 1 | 31.7 | 0.02 | Class 5 | 2610 | 9 | 2601 | 0 | 0.997 | PASS |
| 01-TYPICALFloor | WestN | 41.9 | 0.02 | Class 5 | 2610 | 11 | 2599 | 0 | 0.996 | PASS |
| 02-TOPFloor10 | CENNorth | 257.5 | 0.14 | Class 5 | 2610 | 0 | 2610 | 0 | 1.000 | PASS |
| 02-TOPFloor10 | EastNorth 1 | 41.9 | 0.02 | Class 5 | 2610 | 18 | 2592 | 0 | 0.993 | PASS |
| 02-TOPFloor10 | EastNorth | 31.5 | 0.02 | Class 5 | 2610 | 13 | 2597 | 0 | 0.995 | PASS |
| 02-TOPFloor10 | EastSouth 1 | 26.9 | 0.01 | Class 5 | 2610 | 13 | 2597 | 0 | 0.995 | PASS |
| 02-TOPFloor10 | CENSouth | 228.7 | 0.13 | Class 5 | 2610 | 0 | 2610 | 0 | 1.000 | PASS |
| 02-TOPFloor10 | EastSouth | 41.4 | 0.02 | Class 5 | 2610 | 104 | 2506 | 0 | 0.960 | FAIL |
| 02-TOPFloor10 | WestS 1 | 42.8 | 0.02 | Class 5 | 2610 | 81 | 2529 | 0 | 0.969 | FAIL |
| 02-TOPFloor10 | WestS | 26.6 | 0.01 | Class 5 | 2610 | 14 | 2596 | 0 | 0.995 | PASS |
| 02-TOPFloor10 | WestN 1 | 31.7 | 0.02 | Class 5 | 2610 | 14 | 2596 | 0 | 0.995 | PASS |
| 02-TOPFloor10 | WestN | 41.9 | 0.02 | Class 5 | 2610 | 14 | 2596 | 0 | 0.995 | PASS |
Less than 95% (0.0%) of floor area passes PMV check - Building : FAIL
| Block | Zone | Floor Area (m²) | Fraction Total Floor Area | Building Class | Operation Hours | Operation Hours PMV below -1 | Operation Hours PMV between -1 and 1 | Operation Hours PMV above 1 | Fraction Operation Hours PMV between -1 and 1 | Zone PMV meets Section J target (greater than 98 % Operation Hours between -1 and 1) |
|---|---|---|---|---|---|---|---|---|---|---|
| 00-GROUNDFloor01 | EastNorth 1 | 41.9 | 0.02 | Class 5 | 2610 | 469 | 1519 | 622 | 0.582 | FAIL |
| 00-GROUNDFloor01 | EastNorth | 31.5 | 0.02 | Class 5 | 2610 | 828 | 1191 | 591 | 0.456 | FAIL |
| 00-GROUNDFloor01 | EastSouth 1 | 26.9 | 0.01 | Class 5 | 2610 | 829 | 1191 | 590 | 0.456 | FAIL |
| 00-GROUNDFloor01 | CENSouth | 228.7 | N/A | Class 5 (TO) | 2610 | N/A | N/A | N/A | N/A | N/A |
| 00-GROUNDFloor01 | EastSouth | 41.4 | 0.02 | Class 5 | 2610 | 1041 | 1242 | 327 | 0.476 | FAIL |
| 00-GROUNDFloor01 | WestS 1 | 42.8 | 0.02 | Class 5 | 2610 | 1051 | 1273 | 286 | 0.488 | FAIL |
| 00-GROUNDFloor01 | WestS | 26.6 | 0.01 | Class 5 | 2610 | 839 | 1276 | 495 | 0.489 | FAIL |
| 00-GROUNDFloor01 | WestN 1 | 31.7 | 0.02 | Class 5 | 2610 | 839 | 1275 | 496 | 0.489 | FAIL |
| 00-GROUNDFloor01 | WestN | 41.9 | 0.02 | Class 5 | 2610 | 581 | 1472 | 557 | 0.564 | FAIL |
| 01-TYPICALFloor | CENNorth | 257.5 | 0.14 | Class 5 | 2610 | 100 | 2500 | 10 | 0.958 | FAIL |
| 01-TYPICALFloor | EastNorth 1 | 41.9 | 0.02 | Class 5 | 2610 | 526 | 1519 | 565 | 0.582 | FAIL |
| 01-TYPICALFloor | EastNorth | 31.5 | 0.02 | Class 5 | 2610 | 859 | 1207 | 544 | 0.462 | FAIL |
| 01-TYPICALFloor | EastSouth 1 | 26.9 | 0.01 | Class 5 | 2610 | 861 | 1205 | 544 | 0.462 | FAIL |
| 01-TYPICALFloor | CENSouth | 228.7 | 0.13 | Class 5 | 2610 | 126 | 2474 | 10 | 0.948 | FAIL |
| 01-TYPICALFloor | EastSouth | 41.4 | 0.02 | Class 5 | 2610 | 1065 | 1260 | 285 | 0.483 | FAIL |
| 01-TYPICALFloor | WestS 1 | 42.8 | 0.02 | Class 5 | 2610 | 1074 | 1285 | 251 | 0.492 | FAIL |
| 01-TYPICALFloor | WestS | 26.6 | 0.01 | Class 5 | 2610 | 873 | 1279 | 458 | 0.490 | FAIL |
| 01-TYPICALFloor | WestN 1 | 31.7 | 0.02 | Class 5 | 2610 | 873 | 1278 | 459 | 0.490 | FAIL |
| 01-TYPICALFloor | WestN | 41.9 | 0.02 | Class 5 | 2610 | 635 | 1457 | 518 | 0.558 | FAIL |
| 02-TOPFloor10 | CENNorth | 257.5 | 0.14 | Class 5 | 2610 | 373 | 2213 | 24 | 0.848 | FAIL |
| 02-TOPFloor10 | EastNorth 1 | 41.9 | 0.02 | Class 5 | 2610 | 501 | 1492 | 617 | 0.572 | FAIL |
| 02-TOPFloor10 | EastNorth | 31.5 | 0.02 | Class 5 | 2610 | 828 | 1217 | 565 | 0.466 | FAIL |
| 02-TOPFloor10 | EastSouth 1 | 26.9 | 0.01 | Class 5 | 2610 | 831 | 1213 | 566 | 0.465 | FAIL |
| 02-TOPFloor10 | CENSouth | 228.7 | 0.13 | Class 5 | 2610 | 447 | 2146 | 17 | 0.822 | FAIL |
| 02-TOPFloor10 | EastSouth | 41.4 | 0.02 | Class 5 | 2610 | 1013 | 1255 | 342 | 0.481 | FAIL |
| 02-TOPFloor10 | WestS 1 | 42.8 | 0.02 | Class 5 | 2610 | 1031 | 1284 | 295 | 0.492 | FAIL |
| 02-TOPFloor10 | WestS | 26.6 | 0.01 | Class 5 | 2610 | 853 | 1302 | 455 | 0.499 | FAIL |
| 02-TOPFloor10 | WestN 1 | 31.7 | 0.02 | Class 5 | 2610 | 853 | 1301 | 456 | 0.498 | FAIL |
| 02-TOPFloor10 | WestN | 41.9 | 0.02 | Class 5 | 2610 | 611 | 1451 | 548 | 0.556 | FAIL |
| Block | Zone | Floor Area (m²) | Fraction Total Floor Area | Building Class | Operation Hours | Operation Hours PMV below -0.5 | Operation Hours PMV between -0.5 and 0.5 | Operation Hours PMV above 0.5 | Fraction Operation Hours PMV between -0.5 and 0.5 |
|---|---|---|---|---|---|---|---|---|---|
| 00-GROUNDFloor01 | EastNorth 1 | 41.9 | 0.02 | Class 5 | 2610 | 822 | 592 | 1196 | 0.227 |
| 00-GROUNDFloor01 | EastNorth | 31.5 | 0.02 | Class 5 | 2610 | 1102 | 342 | 1166 | 0.131 |
| 00-GROUNDFloor01 | EastSouth 1 | 26.9 | 0.01 | Class 5 | 2610 | 1102 | 344 | 1164 | 0.132 |
| 00-GROUNDFloor01 | CENSouth | 228.7 | N/A | Class 5 (TO) | 2610 | 575 | 912 | 1123 | 0.349 |
| 00-GROUNDFloor01 | EastSouth | 41.4 | 0.02 | Class 5 | 2610 | 1216 | 423 | 971 | 0.162 |
| 00-GROUNDFloor01 | WestS 1 | 42.8 | 0.02 | Class 5 | 2610 | 1224 | 598 | 788 | 0.229 |
| 00-GROUNDFloor01 | WestS | 26.6 | 0.01 | Class 5 | 2610 | 1102 | 561 | 947 | 0.215 |
| 00-GROUNDFloor01 | WestN 1 | 31.7 | 0.02 | Class 5 | 2610 | 1101 | 562 | 947 | 0.215 |
| 00-GROUNDFloor01 | WestN | 41.9 | 0.02 | Class 5 | 2610 | 900 | 712 | 998 | 0.273 |
| 01-TYPICALFloor | CENNorth | 257.5 | 0.14 | Class 5 | 2610 | 517 | 959 | 1134 | 0.367 |
| 01-TYPICALFloor | EastNorth 1 | 41.9 | 0.02 | Class 5 | 2610 | 870 | 607 | 1133 | 0.233 |
| 01-TYPICALFloor | EastNorth | 31.5 | 0.02 | Class 5 | 2610 | 1120 | 358 | 1132 | 0.137 |
| 01-TYPICALFloor | EastSouth 1 | 26.9 | 0.01 | Class 5 | 2610 | 1123 | 357 | 1130 | 0.137 |
| 01-TYPICALFloor | CENSouth | 228.7 | 0.13 | Class 5 | 2610 | 597 | 899 | 1114 | 0.344 |
| 01-TYPICALFloor | EastSouth | 41.4 | 0.02 | Class 5 | 2610 | 1222 | 484 | 904 | 0.185 |
| 01-TYPICALFloor | WestS 1 | 42.8 | 0.02 | Class 5 | 2610 | 1230 | 640 | 740 | 0.245 |
| 01-TYPICALFloor | WestS | 26.6 | 0.01 | Class 5 | 2610 | 1121 | 590 | 899 | 0.226 |
| 01-TYPICALFloor | WestN 1 | 31.7 | 0.02 | Class 5 | 2610 | 1121 | 587 | 902 | 0.225 |
| 01-TYPICALFloor | WestN | 41.9 | 0.02 | Class 5 | 2610 | 943 | 726 | 941 | 0.278 |
| 02-TOPFloor10 | CENNorth | 257.5 | 0.14 | Class 5 | 2610 | 997 | 634 | 979 | 0.243 |
| 02-TOPFloor10 | EastNorth 1 | 41.9 | 0.02 | Class 5 | 2610 | 831 | 651 | 1128 | 0.249 |
| 02-TOPFloor10 | EastNorth | 31.5 | 0.02 | Class 5 | 2610 | 1092 | 413 | 1105 | 0.158 |
| 02-TOPFloor10 | EastSouth 1 | 26.9 | 0.01 | Class 5 | 2610 | 1092 | 414 | 1104 | 0.159 |
| 02-TOPFloor10 | CENSouth | 228.7 | 0.13 | Class 5 | 2610 | 1071 | 587 | 952 | 0.225 |
| 02-TOPFloor10 | EastSouth | 41.4 | 0.02 | Class 5 | 2610 | 1207 | 504 | 899 | 0.193 |
| 02-TOPFloor10 | WestS 1 | 42.8 | 0.02 | Class 5 | 2610 | 1222 | 675 | 713 | 0.259 |
| 02-TOPFloor10 | WestS | 26.6 | 0.01 | Class 5 | 2610 | 1105 | 682 | 823 | 0.261 |
| 02-TOPFloor10 | WestN 1 | 31.7 | 0.02 | Class 5 | 2610 | 1104 | 681 | 825 | 0.261 |
| 02-TOPFloor10 | WestN | 41.9 | 0.02 | Class 5 | 2610 | 911 | 767 | 932 | 0.294 |
Plugin: DBA NCC Thermal Comfort and Temperature Check Plugin v.0.9.14.0 - part of DBAPlugins v.0.9.14.0 - MachineID (42BBE2).